33kv 35kv 110kv 115kv 132kv 138kv 220kv 230kv Dead Tank Current Transformer Outdoor Electric Substation Equipment
It is oil paper insulation structure. The main insulation is wound from high voltage cable paper, and is placed several capacitor screen of voltage division in the primary insulation, which can improve electric field distributing and decrease the consumption of insulation material. It will be immersed with transformer oil after desiccating under vacuum. It has advantages of stable and reliable performance of insulation, rich successful experience, a long life time.
?Perfect fluidity performance of transformer oil is good for heat dissipation, it also has self recover ability for the failure of partial discharge caused by air bubble and dust.
?The current ratio can be changed easily by switching the connection method of Primary winding to series or parallel.
?Hermetically sealed stainless steel metallic bellows is installed on the top, which protect the transformer oil from moisture and extend the life time, also there is a oil level gauge on the bellows for observing the changing of oil volume.
?Two optimization design external insulation types offered for user for inside and outside electric field without discharge
1. Composite insulator
2. High strength porcelain bushing
?There is a multi function oil drain valve on the base, which make it more convenient for sampling, draining.
?All adopted insulation parts are environmental protection material.
?Secondary terminal board is made of epoxy casting, the seal performance is more reliable.
?The base uses spray painting or hot galvanizing, which gives a high degree of corrosion resistance.
?Fasteners and nameplate are stainless steel.
Product Name 33kv 35kv 110kv 115kv 132kv 138kv 220kv 230kv Dead Tank Current Transformer Outdoor Electric Substation Equipment
Brand Name HYEE
Origin Dalian, CN (Mainland)
Phase Single
Coil Structure Toroidal
Coil Number 1-6
Color Brown/White
Frequency 50/60Hz
Certification ASTA/CTQC/IEC/SGS/ISO9001
Package Wooden Carton
Delivery Time 30 days
Rated frequency,Hz 50; 60
Rated voltage,kV 33or 35 66 or 69 110 or 115 132 or 138 150 220 or 230
Highest voltage for equipment, kV 36 or 40.5 72.5 123 or 126 145 170 245 or 252
Rated power frequency withstand voltage, kV 95 160 230 275 325 460
Rated lightning impulse voltage, kV 200 350 550 650 750 1050
Flashover distance, mm 385 700 1100 1300 1500 2100
Cree. distance, mm W1:810mm
W2:1020mm
W3:1260mm W1:1450
W2:1820
W3:2250 W1:2520
W2:3150
W3:3910 W1:2900
W2:3630
W3:4500 W1:3400
W2:4250
W3:5270 W1:5040
W2:6300
W3:7820
Mechanical load, N 3000 3000 3000 3000 3000 4000
Rated primary current, A 5~5000
Rated secondary current, A 1; 2; 5
Accuracy class 0.1; 0.2; 0.5; 0.2S; 0.5S; 0.5S; 5P; 10P; PX…
Rated output(Recommended value), VA 1A: 10~30 VA
2A: 10~30 VA
5A: 15~50VA
Instrument security factor FS 5; 10
Accuracy limit factors ALF 10,15,20,25,30
Short-time thermal current(Maximum),kA 50kA/3slink:http://www.hyee-current-transformer.com